artículo
Fault tolerant measurement system based on Takagi-Sugeno fuzzy models for a gas turbine in a combined cycle power plant
Fecha
2011Registro en:
10.1016/j.fss.2011.02.011
1872-6801
0165-0114
WOS:000291504700007
Autor
Berrios, Rodrigo
Nunez, Felipe
Cipriano, Aldo
Institución
Resumen
A fault tolerant measurement system for a gas turbine in a combined cycle power plant, based on dynamic models, principal component analysis (PCA) and Q test, is presented. The proposed scheme makes use of a model-based symptom generator, which delivers fault signals obtained by using direct identification of parity relations and structured residuals. Symptoms are then analyzed in a statistical module achieving fault diagnosis and reconstruction of the faulty signals. The scheme presents as main advantage the ability of detecting faults in both input and output sensors due to its particular structure. Tests carried out on the gas turbine of the San Isidro combined cycle power plant in the V Region, Chile, show that Takagi-Sugeno fuzzy models present the best fitting performance and an acceptable computational cost in comparison with autoregressive exogenous. state space, and neural models. Real time software based on this scheme has been developed and connected to Osisoft PI System'. The software is running at Endesa Monitoring and Diagnosis Center in Santiago. Chile. (C) 2011 Elsevier B.V. All rights reserved.