Trabalho de Conclusão de Curso de Graduação
Procedimentos para comissionamento de relés de sobrecorrente
Autor
Fenalte, Letícia Cristina
Institución
Resumen
During the operation of the electrical power system (SEP), there are often protection failures
that can result in shutdowns in the power supply, causing a reduction in quality of service. This
is not common, but it happens because the protection of the SEP has not been correctly scaled
and are usually errors resulting from relay settings that were not correctly commissioned. In this
sense, the objective of this work is to present a methodology for the design of the overcurrent
protection system in a SEP and for the commissioning of digital relays from the data obtained
from fault simulation. Thus, a guide was developed for validation and comparison of the results
obtained through the analysis of the response times of the protection system in the software
DIgSILENT Power Factory and commercial digital relays using a universal relay tester. The
results obtained in a radial system show that the errors of the relay operation times are smaller
than 5% for most faults analyzed..