Actas de congresos
Modal transformation obtained from Clarke's matrix - Asymmetrical three-phase case
Fecha
2007-01-01Registro en:
2007 Ieee Power Engineering Society General Meeting, Vols 1-10. New York: Ieee, p. 220-+, 2007.
1932-5517
WOS:000251345400046
Autor
Universidade Estadual de Londrina (UEL)
Universidade Estadual Paulista (Unesp)
Universidade Estadual de Campinas (UNICAMP)
Institución
Resumen
Some constant matrices can be used as phase-mode transformation matrices for transposed three-phase transmission tines. Clarke's matrix is one of these options. Its application as a phase-mode transformation matrix for untransposed three-phase transmission lines has been analyzed through error and frequency scan comparisons. Based on an actual untransposed asymmetrical three-phase transmission line example, a correction procedure is applied searching for better results from the Clarke's matrix applicaton as a phase-mode transformation matrix. The error analyses are carried out using Clarke's matrix and the new transformation matrices obtained from the correction procedure. Applying Clarke's matrix, the relative errors of the eigenvalue matrix elements can be considered negligible and the relative values of the off-diagonal elements are significant. If the the corrected transformation matrices are used, the relative values of the off-diagonal elements are decreased. Based on the results of these analyses, the homopolar mode is more sensitive to the frequency influence than the two other modes related to three-phase lines.