dc.contributor | Santos, Joaquim Cesar Pizzutti dos | |
dc.contributor | http://lattes.cnpq.br/6591314076760539 | |
dc.contributor | Scherer, Minéia Johann | |
dc.contributor | http://lattes.cnpq.br/2099393137349578 | |
dc.contributor | Vaghetti, Marcos Alberto Oss | |
dc.contributor | http://lattes.cnpq.br/8730453050780826 | |
dc.creator | Christmann, Laura Landerdahl | |
dc.date.accessioned | 2016-04-29 | |
dc.date.available | 2016-04-29 | |
dc.date.created | 2016-04-29 | |
dc.date.issued | 2015-08-28 | |
dc.identifier | CHRISTMANN, Laura Landerdahl. Dimensioning and cooling potential evaluation by chimney effect ventilation in educational building in Santa Maria-RS. 2015. 162 f. Dissertação (Mestrado em Engenharia Civil) - Universidade Federal de Santa Maria, Santa Maria, 2015. | |
dc.identifier | http://repositorio.ufsm.br/handle/1/7904 | |
dc.description.abstract | Natural ventilation is recognized by the scientific community as an important strategy
for the promotion of thermal comfort. It s application in real situations, however, is extremely
low, which is believed to be due to the lack of specific information as well as the lack of
reliability in the success of these strategies. The present study aimed to propose, measure and
evaluate natural ventilation strategy. It was defined the ventilation through the chimney
effect for multiple floors educational buildings, disregarding the wind incidence, in the city of
Santa Maria, RS, Bioclimatic Zone 2. Eight sizes of frames combinations have been proposed
to be analyzed. Simulations with all openings combinations were made through DesignBuilder
software. Based on the simulations results, it was calculated the maximum possible wind
speeds through the strategy. Obtained such values, it was possible to analyze the thermal
comfort gains with the different combinations of frames. It sets up, as the most suitable design
and better performance, the use of all the frames in the same size, this being equivalent to
5,71% of the floor area. Analyzing through adaptive comfort, such configuration has resulted
in reduction of degree-hour of discomfort in 27,9%, 33,3%, 38,8% and 42.7% for one floor,
two floors, three floors and four floors building, respectively, comparing to the building
without the use of the strategy. Since the results for the analyzed situation, compared to the
recommended values by normatives for thermal confort condition, the strategy is evaluate as
good potential and easily aplication in real situations. | |
dc.publisher | Universidade Federal de Santa Maria | |
dc.publisher | BR | |
dc.publisher | Engenharia Civil | |
dc.publisher | UFSM | |
dc.publisher | Programa de Pós-Graduação em Engenharia Civil | |
dc.rights | Acesso Aberto | |
dc.subject | Conforto térmico | |
dc.subject | Ventilação natural | |
dc.subject | Efeito chaminé | |
dc.subject | Conforto adaptativo | |
dc.subject | Thermal comfort | |
dc.subject | Natural ventilation | |
dc.subject | Chimney effect | |
dc.subject | Adaptive comfort | |
dc.title | Dimensionamento e avaliação do potencial de arrefecimento de edificação de ensino através de ventilação por efeito chaminé em Santa Maria - RS | |
dc.type | Dissertação | |