dc.contributor | Cardoso Junior, Ghendy | |
dc.contributor | http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4770600A7 | |
dc.contributor | Mariotto, Lenois | |
dc.contributor | http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4787711P4 | |
dc.contributor | Ferreira, Gustavo Dorneles | |
dc.contributor | http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4214434U8 | |
dc.creator | Muraro, Matias Rossato | |
dc.date.accessioned | 2017-05-30 | |
dc.date.accessioned | 2019-05-24T19:49:07Z | |
dc.date.available | 2017-05-30 | |
dc.date.available | 2019-05-24T19:49:07Z | |
dc.date.created | 2017-05-30 | |
dc.date.issued | 2014-02-27 | |
dc.identifier | MURARO, Matias Rossato. Proposal interconnection protection for islanding detection
in distributed generation systems. 2014. 154 f. Dissertação (Mestrado em Engenharia Elétrica) - Universidade Federal de Santa Maria, Santa Maria, 2014. | |
dc.identifier | http://repositorio.ufsm.br/handle/1/8538 | |
dc.identifier.uri | http://repositorioslatinoamericanos.uchile.cl/handle/2250/2836860 | |
dc.description.abstract | This work presents a methodology for detecting islanding in distributed generation
systems - DG - which use internal combustion engines as primary sources and synchronous
generators connected directly to grid. The proposed method considers the characteristics of this
type of DG, and is based on the analyses of the injected power and voltage level to disable or
enable the under/over frequency protection.
The proposed protection scheme considers the frequency as the main electrical signal,
and has three stages: the first stage is disabled when power injected oscillations are detected, in
the others cases, the stage is enabled; the second stage is normally disabled, it will be enabled
when a balanced voltage is detected after a unbalanced voltage condition and the third stage is
normally enabled and is used to detect large frequency deviations.
The proposed protection was tested over diferentes events, islanding with different load
and generation levels, temporary short-circuit and islanding during short-circuit. The results
show the efficiency and reliability in detecting islanding, presenting no false detections. | |
dc.publisher | Universidade Federal de Santa Maria | |
dc.publisher | BR | |
dc.publisher | Engenharia Elétrica | |
dc.publisher | UFSM | |
dc.publisher | Programa de Pós-Graduação em Engenharia Elétrica | |
dc.rights | Acesso Aberto | |
dc.subject | Geração distribuída | |
dc.subject | Ilhamento | |
dc.subject | Subfrequência e sobrefrequência | |
dc.subject | Oscilação de potência | |
dc.subject | Distributed generation | |
dc.subject | Islanding | |
dc.subject | Underfrequency and overfrequency | |
dc.subject | Power swing | |
dc.title | Uma proposta de interconexão de proteções para detecção de
ilhamento em sistemas de geração distribuída | |
dc.type | Tesis | |