dc.contributor | Santos, Joaquim Cesar Pizzutti dos | |
dc.contributor | http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4792651E5 | |
dc.contributor | Cunha, Eduardo Grala da | |
dc.contributor | http://lattes.cnpq.br/0959256350186452 | |
dc.contributor | Vaghetti, Marcos Alberto Oss | |
dc.contributor | http://lattes.cnpq.br/8730453050780826 | |
dc.creator | Comiran, Sheila | |
dc.date.accessioned | 2015-03-12 | |
dc.date.available | 2015-03-12 | |
dc.date.created | 2015-03-12 | |
dc.date.issued | 2014-02-27 | |
dc.identifier | COMIRAN, Sheila. THERMAL COMFORT AND PERFORMANCE IN HOSPITALS:
CASE STUDY IN THE AREA OF THE HOSPITAL UNIVERSITÁRIO DE
SANTA MARIA, RS. 2014. 156 f. Dissertação (Mestrado em Engenharia Civil) - Universidade Federal de Santa Maria, Santa Maria, 2014. | |
dc.identifier | http://repositorio.ufsm.br/handle/1/7856 | |
dc.description.abstract | The hospital is room for reestablishment of health and therefore its environments should be
comfortable and fit to this function, including thermal comfort. In this context, this paper
presents a review of the conditions for thermal comfort and thermal performance in the
inpatients bedrooms of the University Hospital of Santa Maria (HUSM) city using
measurements, site survey and computer simulation (DesignBuilder software). To analyze
the thermal comfort, human and environmental variables were raised during the summer and
winter of 2012, in four hospital bedrooms with east and west exposure, following the
recommendations of ASHRAE 55 (2010). From the collected data, we calculated the PMV
and PPD through Analysis 1.5 software. Analysis of degree-hours of discomfort with the data
obtained from computational simulation was also performed. To evaluate the thermal
performance tests were carried out by observing the damping and thermal flows, still analysis
was performed closures and opaque areas of the ventilation parameters considering the
simplified method proposed by NBR 15,575 (2013 ) The data found in measurements show
that there is large temperature range in Santa Maria. As for thermal comfort, the results
showed that the analyzed environments are comfortable for the winter period and
uncomfortable for the summer period, showing that the air velocity improves comfort levels
for internal temperatures up to 28° C. Another aspect found is that the thermal damping
obtained demonstrates that the building has great thermal inertia, contributing to thermal
comfort, especially in winter. As for thermal performance, the results of the simplified method
demonstrate that the building meets the minimum performance criteria of ISO 15.575 (2013).
In the simulation to analyze environments performance, through heat fluxes, the results
showed that the greatest gains are achieved through occupation and the solar gains, while
the largest losses occur by air infiltration. These data confirm the results obtained from
analysis of thermal comfort. It is noted that solar gains are positive for the winter period and
the infiltration is negative. However a minimal infiltration must be preserved to hygienic
ventilation for the rooms. During summer time, the use of shading devices is crucial to
reduce solar gain. It was also found that the solar orientation influences the thermal
performance and comfort. Finally, in the case of HUSM, the window frames should be
retrofitted to ensure hygienic ventilation in winter and for summer days, it is necessary to use
artificial cooling, the need for which can be reduced by the implementation of a ventilation
system with control of temperature and improvement in sun protection systems. | |
dc.publisher | Universidade Federal de Santa Maria | |
dc.publisher | BR | |
dc.publisher | Engenharia Civil | |
dc.publisher | UFSM | |
dc.publisher | Programa de Pós-Graduação em Engenharia Civil | |
dc.rights | Acesso Aberto | |
dc.subject | Conforto térmico | |
dc.subject | Desempenho térmico | |
dc.subject | Arquitetura hospitalar | |
dc.subject | Thermal comfort | |
dc.subject | Thermal performance | |
dc.subject | Hospital architecture | |
dc.title | Conforto e desempenho térmico em hospitais:
estudo de caso na área de internação do Hospital
Universitário de Santa Maria/RS | |
dc.type | Dissertação | |