Desarrollo de un Sistema Scada con base de datos según norma ISO 14224 para dos grupos electrógenos de la planta de generación eléctrica del ZPF bloque 18 - Petroamazonas EP.
Fecha
2016-02Registro en:
Oto Topon, Marco Antonio. (2016). Desarrollo de un Sistema Scada con base de datos según norma ISO 14224 para dos grupos electrógenos de la planta de generación eléctrica del ZPF bloque 18 - Petroamazonas EP. Escuela Superior Politécnica de Chimborazo.Riobamba.
Autor
Oto Topon, Marco Antonio
Resumen
This research consisted of the “Development of a SCADA system with database
according to the ISO 14224 standard for two generators of the power plant of ZPF
Block 18 – Petroamazonas EP”, located in Orellana province, this system registers the
fault records of a standardized real-time calculation of key performance indicators
(KPI’s, for its acronym in English) directly from the Human-Machine Interface (HMI), the
selected indicators were: availability, maintainability, reliability, unreliability, Mean Time
To Repair, Mean Time Between Failures, Failure rate, Repair rate and downtime. The
scientific and deductive methods were applied to gather theorical and practical
information necessary for the development, implementation, functional testing and
demostration of the application.
A client-server structure was used, as well as a programmable logic controller (PLC), a
database system SQL (Structured Query Languaje), and development software
SCADA to establish communication among field variables, the tables records and the
HMI, throughout VBA (Visual Basic) programming and SQL statements. After finishing
the implementation the generator reliability results were MG1: 52.37% and MG2
99.02%. In conclusión, the application enabled to obtain key performance indicators in
real time, provide a more reliable database through the fault records base on the ISO
14224:2006 standard, in addition, the two generators Failure Mode and Effects
Analysis were presented. It is recommended to ask maintenance managements
professinals to analyze the indicators results for a correct interpretation, furthermore,
since it is an standardized system, it could be applied to eqipment with similar
characteristics within the oil industry.