dc.contributorGuillén Coello, Hernán Patricio
dc.creatorBarbecho Jimbo, John Fabricio
dc.creatorPérez Quiñónez, Carlos Andrés (PENDIENTE TITULACIÓN)
dc.date.accessioned2023-01-06T21:11:56Z
dc.date.accessioned2023-05-22T15:44:04Z
dc.date.available2023-01-06T21:11:56Z
dc.date.available2023-05-22T15:44:04Z
dc.date.created2023-01-06T21:11:56Z
dc.date.issued2022-12
dc.identifierhttp://dspace.ups.edu.ec/handle/123456789/24013
dc.identifier.urihttps://repositorioslatinoamericanos.uchile.cl/handle/2250/6324579
dc.description.abstractThe present investigative work was developed with the objective of evaluating the existing grounding system in the Industrias Guapán plant and generating an optimization proposal for it. To measure the resistance and resistivity values, the clamp-on method and the Wenner method are applied, respectively. The equipment used in this project is the Amprobe GP-2 Geotest ground resistance and resistivity tester and the HT-T2000 resistance measurement clamp. In addition, Schwarz and Sverak equations are performed for the calculation of the current locations and the projection of the new grounding system. The IEEE std.80: IEEE Guide for Safety in AC Substation Grounding and CPE INEN 19: 2001 Código Eléctrico Nacional are mainly used for this purpose.
dc.languagespa
dc.rightshttp://creativecommons.org/licenses/by-nc-nd/3.0/ec/
dc.rightsopenAccess
dc.rightsAtribución-NoComercial-SinDerivadas 3.0 Ecuador
dc.subjectELECTRICIDAD
dc.subjectCONEXIÓN A TIERRA (ELECTRICIDAD)
dc.subjectRESISTENCIA DE LA TIERRA
dc.subjectNORMAS ELÉCTRICAS - IEEE
dc.titlePropuesta para optimización sistemas de malla de puesta a tierra de las áreas de producción de UCEM - Planta Guapán
dc.typebachelorThesis