dc.contributorBarros, Luciano Sales
dc.contributorhttp://lattes.cnpq.br/2773630729666428
dc.contributorhttp://lattes.cnpq.br/5175817442792763
dc.contributorBarbosa, Daniel
dc.contributorhttp://lattes.cnpq.br/7843695359589199
dc.contributorCosta, Flávio Bezerra
dc.contributorhttp://lattes.cnpq.br/7510091283933216
dc.contributorFernandes, Ricardo Augusto Souza
dc.contributorhttp://lattes.cnpq.br/0880243208789454
dc.creatorQueiroz, Janailson Maciel de
dc.date.accessioned2022-03-09T15:56:04Z
dc.date.accessioned2022-10-06T12:47:55Z
dc.date.available2022-03-09T15:56:04Z
dc.date.available2022-10-06T12:47:55Z
dc.date.created2022-03-09T15:56:04Z
dc.date.issued2021-12-15
dc.identifierQUEIROZ, Janailson Maciel de. Proteção diferencial do DFIG com separação de componentes de sequência do estator e do rotor. 2021. 86f. Dissertação (Mestrado em Engenharia Elétrica e de Computação) - Centro de Tecnologia, Universidade Federal do Rio Grande do Norte, Natal, 2021.
dc.identifierhttps://repositorio.ufrn.br/handle/123456789/46473
dc.identifier.urihttp://repositorioslatinoamericanos.uchile.cl/handle/2250/3959113
dc.description.abstractWith the increasing interest in renewable energy in the world, the importance of research in wind energy, associated methods and technologies have grown. The increase in wind turbines connected to electrical systems also brought new challenges related to the stability of the system and protection of its components. Differential protection is used in many components of electrical systems and for wind turbines based on DFIG this protection was recently proposed. Therefore, this work proposes a new DFIG differential protection scheme using the current sequence components: positive, negative stator and negative rotor. In a simulation with DFIG operating with 1.51 MW, tests of internal and external faults to the protection zone were carried out, of the single-phase and three-phase type, with different levels of voltage drops. Inter-turn faults in the machine rotor and stator were also tested with various levels of failure. Thus, with the proper definition of the operation logic, it was possible to show the effectiveness of the protection, with detection for all faults in the network within the protection zone, considering faults in stator and rotor windings with 5% failure or more.
dc.publisherUniversidade Federal do Rio Grande do Norte
dc.publisherBrasil
dc.publisherUFRN
dc.publisherPROGRAMA DE PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA E DE COMPUTAÇÃO
dc.rightsAcesso Aberto
dc.subjectEnergia eólica
dc.subjectDFIG
dc.subjectComponentes de park
dc.subjectProteção diferencial
dc.subjectFaltas entre espiras
dc.titleProteção diferencial do DFIG com separação de componentes de sequência do estator e do rotor
dc.typemasterThesis


Este ítem pertenece a la siguiente institución