dc.contributorUniversidade Estadual Paulista (Unesp)
dc.date.accessioned2014-05-27T11:30:32Z
dc.date.accessioned2022-10-05T18:58:14Z
dc.date.available2014-05-27T11:30:32Z
dc.date.available2022-10-05T18:58:14Z
dc.date.created2014-05-27T11:30:32Z
dc.date.issued2013-09-01
dc.identifierExperimental Thermal and Fluid Science, v. 49, p. 152-159.
dc.identifier0894-1777
dc.identifierhttp://hdl.handle.net/11449/76403
dc.identifier10.1016/j.expthermflusci.2013.04.013
dc.identifierWOS:000321404800016
dc.identifier2-s2.0-84878929916
dc.identifier9535897335897207
dc.identifier6581222571777811
dc.identifier0000-0001-9606-3265
dc.identifier.urihttp://repositorioslatinoamericanos.uchile.cl/handle/2250/3925293
dc.description.abstractThe factors that have influence on the energy consumption of a small air conditioning system that are worth mentioning are the efficiencies of the compressor, evaporator and condenser, the form that the refrigerant flow is controlled, the fan model used, and climatic conditions. Within the climate issue, an interesting factor is that the relative humidity when it comes to the effect that it causes, especially in the performance of the air condenser, which generally is not considered in the projects. This study aims to evaluate the influence of humidity on the coefficient of system performance (COP), seeking to quantify their influence when it happens. The tests were performed on a testing bench, mounted at the Laboratory for Energy Efficiency (LAMOTRIZ) UNESP-Campus Guaratinguetá. In the study, the wet bulb temperature was ranged, keeping the rotation of the scroll compressor with application of a frequency inverter in its best performance. The test bench is provided with a supervisory system of data collection that is also able to control all functions of the bench. In the results, there was a significant influence, particularly when comparing high humidity conditions with low humidity, noting that only over 65% relative humidity is that significant changes are observed in the COP of the system. © 2013 Elsevier Inc.
dc.languageeng
dc.relationExperimental Thermal and Fluid Science
dc.relation3.204
dc.relation1,271
dc.rightsAcesso restrito
dc.sourceScopus
dc.subjectAir conditioning
dc.subjectEnergy efficiency
dc.subjectRefrigeration
dc.subjectAir humidity conditions
dc.subjectAirconditioning systems
dc.subjectClimatic conditions
dc.subjectEvaporator and condensers
dc.subjectExperimental research
dc.subjectInfluence of humidity
dc.subjectSupervisory systems
dc.subjectWet bulb temperature
dc.subjectEnergy utilization
dc.subjectScroll compressors
dc.titleExperimental research on the influence of the air humidity conditions in an air conditioning system
dc.typeArtigo


Este ítem pertenece a la siguiente institución