dc.contributor | Universidade Estadual Paulista (Unesp) | |
dc.date.accessioned | 2014-05-27T11:17:58Z | |
dc.date.available | 2014-05-27T11:17:58Z | |
dc.date.created | 2014-05-27T11:17:58Z | |
dc.date.issued | 1994-12-01 | |
dc.identifier | Conference Record of IEEE International Symposium on Electrical Insulation, p. 546-549. | |
dc.identifier | 0164-2006 | |
dc.identifier | http://hdl.handle.net/11449/130721 | |
dc.identifier | 10.1109/ELINSL.1994.401397 | |
dc.identifier | WOS:A1994BA96P00132 | |
dc.identifier | 2-s2.0-0028564615 | |
dc.description.abstract | Results of the analysis of dynamic behavior of flashover phenomenon on the high voltage-polluted insulators are presented. These results were taken from a mathematical and an experimental model that introduce the variable thickness influence of the layer pollution deposited on the high-voltage insulator surface. Analysis of the flashover was done by way of introducing a variation in the thickness of the channel of Obenaus' model, simulating a layer pollution of variable thickness. The objective was to obtain a better reproduction of the real layer pollution deposited on the insulator that works in the polluted regions. Two types of thickness variations were used: a sudden variation, using a step; and a soft variation, using a ramp; that were put along the way of the discharge. Comparison between the mathematical and experimental models showed that introduction of a ramp makes Obenaus' model more efficient in analyzing behavior of flashover phenomenon. | |
dc.language | eng | |
dc.publisher | Institute of Electrical and Electronics Engineers (IEEE) | |
dc.relation | Conference Record of IEEE International Symposium on Electrical Insulation | |
dc.rights | Acesso aberto | |
dc.source | Scopus | |
dc.subject | Algorithms | |
dc.subject | Computer simulation | |
dc.subject | Electric discharges | |
dc.subject | Equivalent circuits | |
dc.subject | Geometry | |
dc.subject | Mathematical models | |
dc.subject | Flashover phenomenon | |
dc.subject | High voltage polluted insulators | |
dc.subject | Obenaus model | |
dc.subject | Ramp | |
dc.subject | Step | |
dc.subject | Voltage polarity | |
dc.subject | Electric insulators | |
dc.title | Flashover phenomenon: an analysis with influence of the thickness of the layer pollution of the high voltage polluted insulators | |
dc.type | Actas de congresos | |