Actas de congresos
Robust control applied to power flow control in single-phase inverter with LCL filter, using droop control and D-stability
Date
2012-12-01Registration in:
2012 10th IEEE/IAS International Conference on Industry Applications, INDUSCON 2012.
10.1109/INDUSCON.2012.6451392
WOS:000318021500013
2-s2.0-84874436546
6427185658143370
Author
Universidade Estadual Paulista (UNESP)
Institutions
Abstract
This paper proposes a new methodology to control the power flow between a distributed generator (DG) and the electrical power distribution grid. It is used the droop voltage control to manage the active and reactive power. Through this control a sinusoidal voltage reference is generated to be tracked by voltage loop and this loop generates the current reference for the current loop. The proposed control introduces feed-forward states improving the control performance in order to obtain high quality for the current injected to the grid. The controllers were obtained through the linear matrix inequalities (LMI) using the D-stability analysis to allocate the closed-loop controller poles. Therefore, the results show quick transient response with low oscillations. Thus, this paper presents the proposed control technique, the main simulation results and a prototype with 1000VA was developed in the laboratory in order to demonstrate the feasibility of the proposed control. © 2012 IEEE.
Subjects
Related items
Showing items related by title, author, creator and subject.
-
HPF boost interleaved operating in discontinuous conduction mode for trolleybus application
Gonçalves, Flávio A. S.; Canesin, Carlos A.; Melo, Guilherme A.; De Freitas, Luiz C. G. -
HPF boost interleaved operating in discontinuous conduction mode for trolleybus application
Universidade Estadual Paulista (UNESP) (2009-12-01)This paper deals with results of a research and development (R&D) project in cooperation with Electric Power Distribution Company in São Paulo (Brazil) regarding the development and experimental analysis of a new concept ... -
Variable speed refrigeration system with HPF input rectifier stage
Canesin, C. A.; Gonçalves, F. A S; Leandro, E.; Pinto, J. O P