Artículos de revistas
Partial discharge location in power transformer windings using the wavelet Laplace function
Fecha
2014-06Registro en:
Guillen, Daniel; Idarraga Ospina, Gina; Mombello, Enrique Esteban; Partial discharge location in power transformer windings using the wavelet Laplace function; Elsevier Science Sa; Electric Power Systems Research; 111; 6-2014; 71-77
0378-7796
CONICET Digital
CONICET
Autor
Guillen, Daniel
Idarraga Ospina, Gina
Mombello, Enrique Esteban
Resumen
Insulation system conditions in power transformers can be evaluated by means of partial discharge (PD) analyses. In fact, PD analysis is used to detect premature damage in transformer insulation system to avoid catastrophic faults. Detection and location of PD is a complex problem and has been widely studied by several researchers. A new method for PD location in transformer windings based on Wavelet Laplace (WL) is developed in this paper. First, the PD reference signals are obtained from a lumped parameter model (RLC) and those signals are used to determine the WL parameters, then PD signals are analyzed using the WL and each PD reference signal is replaced by its envelope wavelet transform (EWT) coefficients. Then, if a PD signal occurred in any section of the winding, its location will be defined by Hellinger distance between the EWT coefficients and the new PD reference signals. Results are discussed for PD along the winding and between sections of the winding.