Artículos de revistas
Further improvements on impedance-based fault location for power distribution systems
Fecha
2011Registro en:
IET GENERATION TRANSMISSION & DISTRIBUTION, v.5, n.4, p.467-478, 2011
1751-8687
10.1049/iet-gtd.2010.0446
Autor
SALIM, R. H.
SALIM, K. C. O.
BRETAS, A. S.
Institución
Resumen
In this study, further improvements regarding the fault location problem for power distribution systems are presented. The proposed improvements relate to the capacitive effect consideration on impedance-based fault location methods, by considering an exact line segment model for the distribution line. The proposed developments, which consist of a new formulation for the fault location problem and a new algorithm that considers the line shunt admittance matrix, are presented. The proposed equations are developed for any fault type and result in one single equation for all ground fault types, and another equation for line-to-line faults. Results obtained with the proposed improvements are presented. Also, in order to compare the improvements performance and demonstrate how the line shunt admittance affects the state-of-the-art impedance-based fault location methodologies for distribution systems, the results obtained with two other existing methods are presented. Comparative results show that, in overhead distribution systems with laterals and intermediate loads, the line shunt admittance can significantly affect the state-of-the-art methodologies response, whereas in this case the proposed developments present great improvements by considering this effect.