dc.creatorNAVARRO, Hélio Aparecido
dc.creatorCABEZAS-GÓMEZ, Luben
dc.creatorZOGHBI FILHO, João R. Bastos
dc.creatorRIBATSKI, Gherhardt
dc.creatorSAIZ-JABARDO, José Maria
dc.date.accessioned2012-03-26T01:52:45Z
dc.date.accessioned2018-07-04T13:53:42Z
dc.date.available2012-03-26T01:52:45Z
dc.date.available2018-07-04T13:53:42Z
dc.date.created2012-03-26T01:52:45Z
dc.date.issued2010
dc.identifierJournal of the Brazilian Society of Mechanical Sciences and Engineering, v.32, n.3, p.218-226, 2010
dc.identifier1678-5878
dc.identifierhttp://producao.usp.br/handle/BDPI/4332
dc.identifier10.1590/S1678-58782010000300004
dc.identifierhttp://www.scielo.br/scielo.php?script=sci_arttext&pid=S1678-58782010000300004
dc.identifierhttp://www.scielo.br/pdf/jbsmse/v32n3/v32n3a04.pdf
dc.identifier.urihttp://repositorioslatinoamericanos.uchile.cl/handle/2250/1603133
dc.description.abstractA simulation program based on a control volume analysis has been used in the evaluation of the (ε, NTU) relationship for coils of complex geometry and flow arrangement. The simulation program has been evaluated through simple geometry and flow arrangement coils. The program results compare very well with correlations for simple cross flow coils, and a number of rows up to four. It has also been determined that closed form correlations developed for coils of an infinite number of tube rows are inadequate for those with number of rows in the range between 5 and 10. In addition, it has been found that closed form (ε, NTU) correlations for cross flow coils with the same tube arrangement and number of rows might lead to inaccuracies higher than 10% in the evaluation of the effectiveness of coils of complex flow arrangement.
dc.languageeng
dc.publisherAssociação Brasileira de Engenharia e Ciências Mecânicas - ABCM
dc.relationJournal of the Brazilian Society of Mechanical Sciences and Engineering
dc.rightsCopyright Associação Brasileira de Engenharia e Ciências Mecânicas - ABCM
dc.rightsopenAccess
dc.subjectEffectiveness
dc.subjectNTU
dc.subjectAir coil
dc.titleEffectiveness - NTU data and analysis for air conditioning and refrigeration air coils