dc.creatorVIEIRA, José Carlos M.
dc.creatorSALLES, Diogo
dc.creatorFREITAS, Walmir
dc.creatorFRANÇA, André L. Morelato
dc.date.accessioned2012-03-26T01:52:18Z
dc.date.accessioned2018-07-04T13:53:33Z
dc.date.available2012-03-26T01:52:18Z
dc.date.available2018-07-04T13:53:33Z
dc.date.created2012-03-26T01:52:18Z
dc.date.issued2008
dc.identifierSba: Controle & Automação Sociedade Brasileira de Automatica, v.19, n.2, p.199-213, 2008
dc.identifier0103-1759
dc.identifierhttp://producao.usp.br/handle/BDPI/4299
dc.identifier10.1590/S0103-17592008000200008
dc.identifierhttp://www.scielo.br/scielo.php?script=sci_arttext&pid=S0103-17592008000200008
dc.identifierhttp://www.scielo.br/pdf/ca/v19n2/a08v19n2.pdf
dc.identifier.urihttp://repositorioslatinoamericanos.uchile.cl/handle/2250/1603100
dc.description.abstractAntes de se proceder com a instalação de geração distribuída em redes de distribuição de energia elétrica, engenheiros de proteção devem projetar e parametrizar sistemas de proteção de forma eficiente para desconectar os geradores distribuídos dentro de um tempo pré-determinado, no caso de ocorrência de situações de ilhamento. Tanto o projeto quanto a avaliação de sistemas de proteção anti-ilhamento confiáveis exigem um estudo detalhado envolvendo numerosas simulações dinâmicas, as quais podem demandar muito tempo por parte dos especialistas de proteção. Este artigo tem por objetivo propor um conjunto de fórmulas para reduzir esse número de simulações dinâmicas. Tais fórmulas são capazes de determinar diretamente o comportamento dinâmico dos dispositivos anti-ilhamento mais empregados em geradores síncronos distribuídos: os relés baseados em medidas de freqüência. Elas são obtidas da solução analítica da equação de oscilação da máquina síncrona, juntamente com a solução das equações dos relés. Além disso, as curvas que relacionam o tempo de detecção com o desbalanço de potência ativa, conhecidas como curvas de desempenho, são empregadas para avaliar a exatidão das fórmulas. Tais curvas são obtidas tanto por simulação dinâmica quanto pelas fórmulas propostas, assim uma comparação abrangente pode ser realizada. Os dispositivos de proteção contra ilhamentos analisados neste trabalho são o relé de sub/sobre freqüência, o relé de taxa de variação de freqüência (em inglês, ROCOF relay - Rate Of Change Of Frequency relay) e o relé de deslocamento de fase ou "salto de vetor" (em inglês Vector Surge, Vector Shift ou Voltage Jump relay).
dc.description.abstractPrior to the installation of distributed generation in distribution networks, protection engineers must design and adjust efficiently protection systems to disconnect all distributed generators within acceptable time frame in case of islanding occurrences. Designing and evaluating reliable protection systems require numerous repeated dynamic simulations, which may be very time consuming. This paper aims to reduce the number of simulations necessary to design anti-islanding protection of distributed generators by proposing a set of formulas that determine directly the dynamic behavior of the most employed anti-islanding devices in synchronous-based distributed generation: frequency-based relays. Such formulas are derived from the solution of the synchronous machine and relays equations. Moreover, the detection time versus active power imbalance curves, known as performance curves, are employed to evaluate the accuracy level of these formulas. These curves are obtained by non-linear dynamic simulations as well as by the proposed formulas, thus a thorough comparison can be done. The frequency-based relays analyzed are: under and over-frequency relays, rate of change of frequency relays (ROCOF relays) and vector surge or vector jump relays (VS relays).
dc.languagepor
dc.publisherSociedade Brasileira de Automática
dc.relationSba: Controle & Automação Sociedade Brasileira de Automatica
dc.rightsCopyright Sociedade Brasileira de Automática
dc.rightsopenAccess
dc.subjectGeração distribuída
dc.subjectDetecção de ilhamento
dc.subjectMáquinas síncronas
dc.subjectProteção
dc.subjectDistributed generation
dc.subjectIslanding detection
dc.subjectSynchronous machines
dc.subjectProtection
dc.titleUm método prático para a definição dos ajustes de relés baseados em medidas de freqüência usados para detecção de ilhamento de geração distribuída
dc.typeArtículos de revistas


Este ítem pertenece a la siguiente institución