dc.identifier | Cortés Rojas, Erika Carolina. (2015). Diseño del sistema de tratamiento para los residuos recolectados por el hidrosuccionador de la EP- EMAPAG del Cantón Guaranda año 2015. Escuela Superior Politécnica de Chimborazo. Riobamba. | |
dc.identifier | http://dspace.espoch.edu.ec/handle/123456789/4880 | |
dc.identifier.uri | http://repositorioslatinoamericanos.uchile.cl/handle/2250/1061598 | |
dc.description | El diseño del sistema de tratamiento para los residuos recolectados por el hidrosuccionador de la
EP-EMAPAG del Cantón Guaranda. Se recopiló la información técnica del equipo,
posteriormente se tomaron 7 muestras en un periodo de 6 meses, considerando los puntos donde
el hidrosuccionador operaba. Se utilizó la última muestra, para realizar análisis específicos de
floculación, coagulación y sedimentación, debido a que presentaba mayor alteración en las
propiedades organolépticas, estéticas, físicas, químicas y microbiológicas. Para determinar el
volumen de agua residual recolectada se registraron los valores de volumen obtenidos durante el
periodo de aforo y los valores históricos comprendidos entre octubre del 2014 a marzo del 2015.
En la medición del caudal para el agua residual se calculó a partir del volumen semanal máximo
registrado y por recomendación de la Dirección Técnica se consideró medir el caudal
semanalmente. Los resultados de la caracterización realizada al agua residual dieron las
siguientes concentraciones fuera de los límites permisibles según la Tabla 12 Anexo 1, Libro VI
de la norma TULSMA: color 480NTU, coliformes fecales 258Nmp/100ml, demanda
bioquímica de oxígeno 11580mg/L, demanda química de oxígeno 5089mg/L, nitrógeno total
18,54mg/L, solidos suspendidos 228,38mg/L considerando además algunos parámetros que no
se encuentran establecidos en esta normativa pero que son importantes por estética e indicadores
en la calidad del agua como: turbiedad 156,43NTU, coliformes totales 760Nmp/100ml, oxígeno
disuelto 0,84mg/L. A partir de la caracterización primaria y simulación de procesos de
tratamiento se concluyó establecer las siguientes unidades: rejillas, sedimentador convencional,
tanque de almacenamiento y coagulación, filtro anaerobio de flujo ascendente, filtro lento de
arena y carbón activado, tanque de cloración. El diseño se realizó usando el Software AutoCAD
2013. Se recomienda a la Empresa Municipal de Agua Potable y Alcantarillado de Guaranda
implementar la planta de tratamiento para reducir el impacto ambiental y la proliferación de
patógenos. | |
dc.description | “Design of the treatment system for waste collected by the EP-EMAPAG hydro-suctioner,
Guaranda canton”. Technical information or equipment was collected, then 7 samples were
taken over a period of six months, considering the points where the hydro-suctioner operated.
The last sample was used for specific analysis of flocculation, coagulation and sedimentation,
because it showed more alterations in the organoleptic, aesthetic, physical, chemical and
microbiological properties. In order to determine the volume of wastewater collected volume
values obtained during the gauging period and the historical values between October 2014 and
March 2015. Flow measurement of the Technical Management was considered weekly measure
the flow. The results of the characterization made to the wastewater had the following
concentration outside the permissible limits according to Table 12, Annex 1, Book VI of the
TULSMA standard: Color 480NTU, 258 fecal coliforms Nmp/100ml, DOB 11580mg/L,
chemical oxygen demand 5089mg/L, total nitrogen 18,54mg/L, suspended solids 228,38mg/L
also considering some parameters that are not established in these regulations but are important
for aesthetics and indicators in water quality as: 156,43NTU turbidity, total coliforms
760Nmp/100ml, dissolved oxygen 0,84mg/L. From the simulation of treatment processes and
primary characterization it was determined to establish the following units: girds, conventional
settler, storage and coagulation tank, upflow anaerobic filter, slow filter of sand and activated
coal, chlorination tank. The design was performed using the software AutoCAD 2013. It is
recommended that the company implement treatment plant to reduce environmental impact and
spread of pathogens. | |
dc.language | spa | |
dc.publisher | Escuela Superior Politécnica de Chimborazo | |
dc.relation | UDCTFC;236T0176 | |
dc.rights | openAccess | |
dc.rights | http://creativecommons.org/licenses/by-nc-sa/3.0/ec/ | |
dc.subject | PLANTA DE TRATAMIENTO | |
dc.subject | HIDROSUCCIONADOR | |
dc.subject | AGUA RESIDUAL | |
dc.subject | DEMANDA BIOQUÍMICA DE OXÍGENO | |
dc.subject | SEDIMENTADOR CONVENCIONAL | |
dc.subject | TANQUE DE ALMACENAMIENTO Y COAGULACIÓN | |
dc.subject | FILTRO ANAEROBIO DE FLUJO ASCENDENTE | |
dc.subject | FILTRO LENTO DE ARENA Y CARBÓN ACTIVADO | |
dc.title | Diseño del sistema de tratamiento para los residuos recolectados por el hidrosuccionador de la EP- EMAPAG del Cantón Guaranda año 2015. | |
dc.type | Tesis | |