Otro
The use of current transformers for noise detection due to sparking in insulators strings in high voltage transmission lines
Registration in:
2010 International Conference on High Voltage Engineering and Application, ICHVE 2010, p. 57-60.
10.1109/ICHVE.2010.5640865
2-s2.0-78650590280
Author
Adami, José Feliciano
Martinez, Manuel Luiz Barreira
Bertoleti, Pedro Henrique Fonseca
Senne, Ithamar
Abstract
In a general way, in an electric power utility the current transformers (CT) are used to measurement and protection of transmission lines (TL) 1 The Power Line Carriers systems (PLC) are used for communication between electrical substations and transmission line protection. However, with the increasing use of optical fiber to communication (due mainly to its high data transmission rate and low signal-noise relation) this application loses potentiality. Therefore, other functions must be defined to equipments that are still in using, one of them is detecting faults (short-circuits) and transmission lines insulator strings damages 2. The purpose of this paper is to verify the possibility of using the path to the ground offered by the CTs instead of capacitive couplings / capacitive potential transformers to detect damaged insulators, since the current transformers are always present in all transmission lines (TL's) bays. To this a comparison between this new proposal and the PLC previous proposed system 2 is shown, evaluating the economical and technical points of view. ©2010 IEEE.
Subjects
Related items
Showing items related by title, author, creator and subject.
-
The use of current transformers for noise detection due to sparking in insulators strings in high voltage transmission lines
Universidade Estadual Paulista (Unesp); U. Federal Itajubá; AES Sul (2010-12-31)In a general way, in an electric power utility the current transformers (CT) are used to measurement and protection of transmission lines (TL) 1 The Power Line Carriers systems (PLC) are used for communication between ... -
The use of current transformers for noise detection due to sparking in insulators strings in high voltage transmission lines
Universidade Estadual Paulista (Unesp); U. Federal Itajubá; AES Sul (2010-12-31)In a general way, in an electric power utility the current transformers (CT) are used to measurement and protection of transmission lines (TL) 1 The Power Line Carriers systems (PLC) are used for communication between ... -