dc.contributorUniversidade Estadual Paulista (Unesp)
dc.creatorAraujo, A. R. J. de [UNESP]
dc.creatorSilva, R. C. da [UNESP]
dc.creatorKurokawa, S. [UNESP]
dc.date2015-10-22T07:25:11Z
dc.date2015-10-22T07:25:11Z
dc.date2015-04-01
dc.date.accessioned2023-09-12T07:04:35Z
dc.date.available2023-09-12T07:04:35Z
dc.identifierhttp://www.ewh.ieee.org/reg/9/etrans/ieee/issues/vol13/vol13issue4April2015/20JustodeAraujo.htm
dc.identifierIeee Latin America Transactions. Piscataway: Ieee-inst Electrical Electronics Engineers Inc, v. 13, n. 4, p. 1029-1034, 2015.
dc.identifier1548-0992
dc.identifierhttp://hdl.handle.net/11449/129872
dc.identifierWOS:000354483000019
dc.identifier4830845230549223
dc.identifier.urihttps://repositorioslatinoamericanos.uchile.cl/handle/2250/8779201
dc.descriptionVoltages and currents in the transmission line are described by differential equations that are difficult to solve due soil and skin effect that has to be considered for accurate results, but it increases their complexity. Therefore there are some models to study the voltages and currents along in transmission line. The distributed parameters model that transforms the equations in time domain to the frequency domain and once the solutions are obtained, they are converted to time domain using the Inverse Laplace Transform using numerical methods. Another model is named lumped parameters model and it considers the transmission line represented by a pi-circuit cascade and the currents and voltages are described by state equations. In the simulations using the lumped parameters model, it can be observed the presence of spurious oscillations that are independent of the quantity of pi-circuits used and do not represent the real value of the transient. In this work will be projected a passive low-pass filter directly inserted in the lumped parameters model to reduce the spurious oscillations in the simulations, making this model more accurate and reliable for studying the electromagnetic transients in power systems.
dc.descriptionUniversidade Estadual Paulista UNESP, Ilha Solteira, SP, Brazil
dc.format1029-1034
dc.languagepor
dc.publisherIeee-inst Electrical Electronics Engineers Inc
dc.relationIeee Latin America Transactions
dc.relation0.502
dc.relation0,253
dc.rightsAcesso restrito
dc.sourceWeb of Science
dc.subjectElectromagnetic transients
dc.subjectTransmission lines
dc.subjectDistributed parameters
dc.subjectLumped parameters
dc.subjectLow-pass filter
dc.titleReducing the spurious oscillations in the lumped parameters model using low-pass filter
dc.typeArtigo