Actas de congresos
Estimation of parameters for faulted transposed transmission lines
Fecha
2018-01-01Registro en:
2018 Ieee Electrical Power And Energy Conference (epec). New York: Ieee, 6 p., 2018.
2381-2842
WOS:000458814200055
Autor
Universidade Estadual Paulista (Unesp)
Institución
Resumen
This paper presents a method to estimate transmission line parameters for transposed lines from faulted current and voltage measurements at the line's terminals, in the time domain. The measurements are transformed to the modal domain, using Clarke's transformation matrix, and related to the modal impedance and admittance using the pi-circuit representation. The lumped modal parameters calculated by the least square method are firstly distributed along the line and finally converted to the phase domain. The method is tested for both short and open circuit faults and proved invariant and precise for transmission lines within 800km of length.