Análise da concepção e comportamento do sistema de aproveitamento de água de chuva em operação na UFMT, Campus Cuiabá
Fecha
2016-05-13Registro en:
NUNES, Juliana Gervasio. Análise da concepção e comportamento do sistema de aproveitamento de água de chuva em operação na UFMT, Campus Cuiabá. 2016. 109 f. Dissertação (Mestrado em Engenharia de Edificações e Ambiental) - Universidade Federal de Mato Grosso, Faculdade de Arquitetura, Engenharia e Tecnologia, Cuiabá, 2016.
Autor
Lima, Eliana Beatriz Nunes Rondon
http://lattes.cnpq.br/9641750996845089
Lima, Eliana Beatriz Nunes Rondon
292.811.641-91
http://lattes.cnpq.br/9641750996845089
Santos, Daniel Costa dos
451.775.970-91
http://lattes.cnpq.br/5356137426989372
292.811.641-91
Morais, Eduardo Beraldo de
287.300.588-21
http://lattes.cnpq.br/2910407574938593
Carmo Junior, Gersina Nobre da Rocha
486.674.801-00
http://lattes.cnpq.br/8920941888298909
Institución
Resumen
The scarcity water ́s problem requires conservation measures of water resource are more and
better implemented, in order to promote the sustainability of the environment in which they
operate. Within this context the higher education institutions (IES) has a fundamental role and
should be like an example of responsibility about the environment. Seeking to assume this
responsibility and to promote and boost sustainable development, the Federal University of
Mato Grosso, Cuiabá ́s campus, aims to establish and diagnose sustainable initiatives for
conservation and rationalization of water. Among the points to be diagnosed is the pilot system
behavior using rain waters in the Faculty of Economics (FE). The system consists of asbestos
cement roof, metal chutes, vertical conductors PVC, lower reservoir with a volume of 20m3
automated discharge, and two reservoirs 3.m3 (one to rainwater and other to drinking water) to
supply the toilets. Thus, this study aims to analyze the behavior of this system through
performance indicators, from the definition of usable potential of rain, the monitoring of water
consumption in the FE building and rating the water quality in the reservoir at the Faculty of
Economics for non-potable purposes. In this intention, were performed about pH, turbidity,
color, conductivity, BOD, COD, hardness, solids and soluble toais, total coliforms and
Escherichia coli, as well as data collection from hydrometers of drinking water, and rainwater
hydrometer to supply toilets installed in the building. The rainwater potential of use was
determined based on rainfall of Cuiaba - MT following the recommended by NBR -
15.527/2007. Thus, the analysis of rainfall revealed a high concentration of the precipitate
volume in a single quarter (67.6% in 2015), and a dry quarter with an interval of up to 31 days
without rain. By monitoring the water consumption observed that the system serves 21% of
total consumption in the FE building and 62% of the consumed only in toilets. The analysis of
physical-chemical and microbiological variables indicated a quality commitment, especially
about the variables that are associated with the presence of solids and impurities originating
from roof washing, as a result of non-compliance with some aspects recommended by NBR
15527/2007. The return on investment occurs in a period over 23 years. Evaluation of results
subsidized propositions that contribute to the development of goals to UFMT ́s Water Plan