Indicador de inconformidades em instalações elétricas de baixa tensão
Fecha
2016-01-28Registro en:
LIMA, Alfredo Rodrigues de. Indicador de inconformidades em instalações elétricas de baixa tensão. 2016. 131f. Dissertação (Mestrado Profissional em Energia Elétrica) - Centro de Tecnologia, Universidade Federal do Rio Grande do Norte, Natal, 2016.
Autor
Lima, Alfredo Rodrigues de
Resumen
With the progress of devices technology, generation and use of energy ways, power
quality parameters start to influence more significantly the various kinds of power
consumers. Currently, there are many types of devices that analyze power quality.
However, there is a need to create devices, and perform measurements and calculate
parameters, find flaws, suggest changes, and to support the management of the
installation. In addition, you must ensure that such devices are accessible. To maintain
this balance, one magnitude measuring method should be used which does not require
great resources processing or memory. The work shows that application of the Goertzel
algorithm, compared with the commonly used FFT allows measurements to be made
using much less hardware resources, available memory space to implement
management functions. The first point of the work is the research of troubles that are
more common for low voltage consumers. Then we propose the functional diagram
indicate what will be measured, calculated, what problems will be detected and that
solutions can be found. Through the Goertzel algorithm simulation using Scilab, is
possible to calculate frequency components of a distorted signal with satisfactory results.
Finally, the prototype is assembled and tests are carried out by adjusting the parameters
necessary for one to maintain a reliable device without increasing its cost.