Artículos de revistas
Combined solution for fault location in three-terminal lines based on wavelet transforms
Fecha
2010Registro en:
IET GENERATION TRANSMISSION & DISTRIBUTION, v.4, n.1, p.94-103, 2010
1751-8687
10.1049/iet-gtd.2009.0249
Autor
SILVA, M. da
COURY, D. V.
OLESKOVICZ, M.
SEGATTO, E. C.
Institución
Resumen
This work presents the study and development of a combined fault location scheme for three-terminal transmission lines using wavelet transforms (WTs). The methodology is based on the low- and high-frequency components of the transient signals originated from fault situations registered in the terminals of a system. By processing these signals and using the WT, it is possible to determine the time of travelling waves of voltages and/or currents from the fault point to the terminals, as well as estimate the fundamental frequency components. A new approach presents a reliable and accurate fault location scheme combining some different solutions. The main idea is to have a decision routine in order to select which method should be used in each situation presented to the algorithm. The combined algorithm was tested for different fault conditions by simulations using the ATP (Alternative Transients Program) software. The results obtained are promising and demonstrate a highly satisfactory degree of accuracy and reliability of the proposed method.