Artículos de revistas
Behavior of overhead transmission line parameters on the presence of ground-wires
Registro en:
Ieee Transactions On Power Delivery. Ieee-inst Electrical Electronics Engineers Inc, v. 20, n. 2, n. 1669, n. 1676, 2005.
0885-8977
WOS:000228096100059
10.1109/TPWRD.2004.833916
Autor
Kurokawa, S
Pissolato, J
Tavares, MC
Portela, CM
Prado, AJ
Institución
Resumen
Initially this paper shows the ground wire reduction process for generic multiphase transmission lines and after, the ground wire reduction process for a specilic 440-kV three-phase overhead transmission line. Following this, the influence of the ground wire reduction process considering two situations is shown: first, considering frequency independence and second, when these parameters are considered as frequency dependent. This paper presents analytical results for generic multiphase transmission lines. For a specific 440-kV three-phase overhead transmission line, analytical and graphic results are shown considering real data for every frequency between 10 Hz and 1 MHz. 20 2 2 1669 1676