Artículos de revistas
Influence of Voltage Positive Feedback Anti-Islanding Scheme on Inverter-Based Distributed Generator Stability
Registro en:
Ieee Transactions On Power Delivery. Ieee-inst Electrical Electronics Engineers Inc, v. 24, n. 2, n. 972, n. 973, 2009.
0885-8977
WOS:000265093000057
10.1109/TPWRD.2009.2013373
Autor
Wang, XY
Freitas, W
Institución
Resumen
This letter investigates the influence of the voltage positive feedback anti-islanding scheme on the stability of inverter-based distributed generators (DGs). Modal analysis is used to determine the relationship between the positive feedback gain of the anti-islanding control and the stability limit. It was found that strong positive feedback gain will destabilize the distribution generator when the power transferred from the distribution system to the DG local load is small. 24 2 972 973 Natural Resources Canada [PESL-00114-2007] Natural Resources Canada [PESL-00114-2007]